Energy performance investigation of a district cooling system

A. Bukshaisha, A. H. Beitelmal

Research output: Chapter in Book/Report/Conference proceedingConference contributionpeer-review

Abstract

A steady-state model is developed to investigate the effect of the chilled water supply temperature and the inlet condenser water temperature on the performance of the centralized chiller system. The current results show that increasing the chilled water supply temperature by 1 degrees C increases the coefficient of performance (COP) of the chiller by 1% to 3% and reduces the total cooling system power consumption by an average of 2% when operating the chiller system at the design capacity level. Decreasing the entering condenser water temperature by 1 degrees C increases the chiller COP by an average of 2% and reduces the total power demand by an average of 1.5%. The reduction in the power consumption translates into a measurable annual reduction in CO2 emissions. The amount of CO2 emissions reduction depends on the type of fuel used to produce the electricity available for the chiller system. The current results also show that the chilled water temperature can be safely raised to a higher set point temperature than the industry standard set point of 5-6 degrees C while preserving the cooling capacity requirements. In addition, the current results suggest that chilled water supply temperature set point of 8 degrees C to 10 degrees C (46 degrees F to 50 degrees F) would provide energy savings of 5% and 9.8%, respectively, over the base case used of 6 degrees C while reducing the carbon footprint by the same percentage.
Original languageEnglish
Title of host publicationEnergy Production And Management In The 21st Century Ii: The Quest For Sustainable Energy
EditorsCA Brebbia, F Polonara, ER Magaril, G Passerini
PublisherWit Press
Pages157-166
Number of pages10
Volume205
ISBN (Electronic)978-1-78466-108-3
ISBN (Print)978-1-78466-107-6
DOIs
Publication statusPublished - 2016
Event2nd International Conference on Energy Production and Management in the 21st Century - The Quest for Sustainable Energy (EQ) - Ancona, Italy
Duration: 6 Sept 20168 Sept 2016

Publication series

NameWit Transactions On Ecology And The Environment

Conference

Conference2nd International Conference on Energy Production and Management in the 21st Century - The Quest for Sustainable Energy (EQ)
Country/TerritoryItaly
CityAncona
Period6/09/168/09/16

Keywords

  • Hvac
  • Centralized chiller system
  • District cooling
  • Energy efficiency

Fingerprint

Dive into the research topics of 'Energy performance investigation of a district cooling system'. Together they form a unique fingerprint.

Cite this